Why UniStream, and not just any PLC?
Most PLCs with an MQTT client connect to DCC through Generic MQTT. That works well, but the PLC programmer has to map tags into DCC's JSON payload format, typically in PLC code or a function block. UniLogic publishes data in its own fixed format, one tag or one struct per topic, so DCC handles the mapping instead.
- Generic MQTT (e.g. Siemens, Beckhoff, Codesys PLCs): you build the DCC JSON payload in the PLC
- Unitronics UniStream: you select tags or structs in UniLogic, and DCC maps them to sample points automatically
Same secure MQTT connection, less PLC programming.
What UniStream brings
According to Unitronics, UniStream combines PLC, HMI and I/O in one platform, and all models are programmed in UniLogic.
- PLC, HMI and I/O in one unit on the Built-in series, or a compact PLC with a virtual HMI on UniStream PLC models
- MQTT client built into UniLogic, alongside Modbus, EtherNet/IP, CANopen, OPC UA, REST API and SQL
- UniLogic software, updates and technical support provided by Unitronics at no charge
- One software environment for ladder, HMI screens, hardware configuration and communication
What DCC adds
DCC turns UniStream data into fleet and machine dashboards, historical trends, alarms by email and SMS, scheduled reports and role-based customer access, and you can work with the data from an AI assistant through the DCC MCP server.
How the native integration works
- Publish tags from UniLogic in Json format
- Single tag on its own topic: the sample point is named after the topic below the device's base topic, e.g. PK1_LoadPercent
- Struct: each struct member becomes a sample point named after its key
- Numbers, true/false values and text are all supported
- Timestamps are set by DCC on arrival
Use one format per tag: either its own topic or a struct member. Keep structs flat, since nested structs and arrays are not supported. UniStream has a limit on struct size, so split very large structs into several smaller ones.
How the connection is secured
- Outbound MQTT over TLS from the PLC, so no inbound ports are opened at the machine
- Username and password authentication on the DCC broker
- The DCC CA certificate is loaded in UniLogic under MQTT/SSL, CA certificate only
- No VPN into the machine network and no remote access to the PLC is required for data collection
Connect UniStream to DCC
- In DCC, create a Unitronics UniStream device and download the connection package with credentials and CA certificate
- In UniLogic, add the DCC broker under MQTT with SSL and the CA certificate
- Add publications in Json format, as single tags or structs, on the device's base topic
- Download the project to the PLC and verify incoming values in DCC Live View
Model scope
The integration has been tested with the UniStream USC-B10-B1. MQTT is part of UniLogic and works the same way across UniStream models, but other models have not been tested yet. Unitronics Vision, Samba and Jazz controllers have no native MQTT client and are not covered by this integration.
Frequently asked questions
Why is a PLC listed among the gateways?
Because the gateway function is built into the UniStream PLC, and DCC has a dedicated device type for it that reads UniLogic's own MQTT JSON. Other PLCs are not listed individually because they connect through Generic MQTT.
Can I connect a Siemens or other PLC the same way?
Yes, any PLC with an MQTT client can publish to DCC through Generic MQTT. The difference is that the PLC must send DCC's JSON payload format, while UniStream publications are mapped by DCC automatically.
Do I need a gateway or edge device next to the UniStream?
No. The PLC connects outbound to the DCC MQTT broker over TLS. You only need internet access from the machine network.
Which UniStream models are supported?
The integration is tested with the USC-B10-B1. MQTT works the same way across UniStream models in UniLogic, but other models have not been tested yet. Vision, Samba and Jazz are not supported.
Can I publish a struct instead of single tags?
Yes. Each member of a flat struct becomes its own sample point. Nested structs and arrays are not supported, and very large structs should be split, since UniStream limits struct size.